| Feature | Specification |
|---|---|
| Number of channels | One |
| Location of load | Zone 0, IIC, T4-6 hazardous area (if certified) or Div.1, Group A hazardous location |
| Minimum output voltage | 7.8V at 48mA |
| Maximum output voltage | 24V from 300Ω |
| Maximum off-state output voltage | 4V from 300Ω |
| Current limit | 48mA minimum |
| Output ripple | < 0.5% of maximum output (peak-to-peak) |
| Response time | Within 10% of final value within 100ms |
| LED indicators | Green (power), Yellow (output status) |
| Maximum current consumption | 100mA at 24V dc |
| Power dissipation | 1.3W (typical), 1.9W (worst case) |
| Safety parameters | Uo=25V, Io=83.3mA, Po=0.52W, Um=253V rms or dc |
| Shipping weight | 1 Kg |
Contact Us at Any Time